Memo-Graph S 7 Procedure in operation
Endress+Hauser 77
The following functions are available:
• Update ATA flash: closes the current block in the memory and saves it onto the card including
the most recently saved values independent of the data quantity.
Save set-up to ATA flash or load set-up to ATA flash: this copies all device settings (except IDs of
the users / administrators approved for the device) onto the card or reads in the device's set-up
data into a new device (important, e.g. in case of replacement).
Save IDs to ATA flash or load IDs from ATA flash: this copies all IDs / user names onto the card
or reads it into a new device (important, e.g. in case of replacement).
• ATA flash information: provides information about card capacity, memory used, etc.
Hardware
Information about memory capacity, device version, memory card, etc. Important for questions
about the device, service, option upgrades, etc.
!
Note!
• Measured values are not lost, even in the event of a power failure (buffering of the internal
memory).
• The memory information accounts for the currently-saved device settings under the specified
requirements (see “Technical data - Memory”).
• Have you just made changes that have not yet been saved? The correct memory information is
then not available until you return from the set-up to normal operation (keep pressing “ESC”) and
save the changes with “Yes”. See also “Adjust device settings - Set-up - Input principle”.
• The available memory interval is reduced if
- Limit values/events are saved or monitored
- Digital inputs are used
- Signal analyses are activated
- Other groups are saved more quickly
Zoom display
Switched on: in curve display, i.e. in the “Plot in zones” setting, displays appear in the relevant
colour, alternately from channel designation to measured value for channels' zoom range. This
makes it easy to tell which signal range is displayed in the window.
Relays/OC: Simulate power failure / Restore normal operation
Depending on the device set-up, a power failure is simulated for the corresponding relay or normal
operation is restored.
7.2.6 Set-up
Viewing or changing device setting (for details see “Adjusting device settings - Set-up”)