Proline Promag 50W, 53W
20 Endress+Hauser
Degree of protection • Standard: IP 67 (NEMA 4X) for transmitter and sensor
• Optional: IP 68 (NEMA 6P) for sensor in remote version
Shock and vibration resistance Acceleration up to 2 g by analogy with IEC 60068-2-6.
Electromagnetic compatibility
(EMC)
To EN 61326/A1 and NAMUR recommendation NE 21.
Process conditions
Medium temperature range The permissible medium temperature depends on the measuring-tube lining:
• 0...+80 °C for hard rubber (DN 65...2000)
• −20...+50 °C for polyurethane (DN 25...1000)
Conductivity Minimum conductivity:
≥ 5 µS/cm for liquids generally
≥ 20 µS/cm for demineralised water
Note that in the case of the remote version, the minimum conductivity is also influenced by the length of the
connecting cable → see “Length of connecting cable”
Medium pressure range
(nominal pressure)
EN 1092-1 (DIN 2501):
PN 6 (DN 1200…2000)
PN 10 (DN 200…2000)
PN 16 (DN 65…2000)
PN 25 (DN 200...1000)
PN 40 (DN 25…150)
ANSI B16.5:
Class 150 (1…24")
Class 300 (1…6")
AWWA:
Class D (28…78")
JIS B2238:
10K (DN 50…300)
20K (DN 25…300)
AS 2129:
Table E (DN 80, 100, 150...400, 500, 600)
AS 4087:
Cl. 14 (DN 80, 100, 150...400, 500, 600)
Pressure tightness
(liner)
Nominal diameter Measuring tube
lining
Resistance to partial vacuum of measuring tube lining
Limit values for abs. pressure [mbar] at various
fluid temperatures
[mm] [inch] 25 °C 50 °C 80 °C 100 °C 130 °C 150 °C 180 °C
25…1000 1…40" Polyurethane 0 0 −−−−−
65…2000 3…78" Hard rubber 0 0 0 −−−−